Aerocel-CG
Closed Cell Elastomeric Thermal lnsulation for HVAC & Refrigeration
Aerocel-CG Tube and Sheet lnsulation is a flexible, closed cell and light weight elastomeric material designed for insulating liquid cooling and heating lines. Aerocel-CG is available in 3/8", 1/2", 3/4" and 1" thickness, and popular sizes up to 1 1/8" ID. The closed-cell structure of Aerocel Pipe lnsulation makes it an efficient insulation.
Aerocel-CG is manufactured to consistently provide actual values on these key performance criteria for mechanical system insulation:
Thermal Conductivity: 0.245 Water Vapor transmission: <.05 Perm-Inch Fire Rating: F/S 25/50
Aerocel-CG Pipe Insulation, in 3/8", 1/2", 3/4" and 1" thicknesses has a flame spread rating of 25 or less and a smoke developed rating of 50 or less as tested by ASTM E 84 Surface Burning Characteristics of Building Materials.
Note: Numerical flammability ratings alone may not define the performance under actual fire conditions. They are provided only for use in the selection of products to meet limits specified.
Key Features
- Best UV Resistance
- Low thermal conductivity
- Easy to install
- 25/50 rated
- Versatile, for heating, AC, plumbing
Uses
Aerocel ® CG Pipe Insulation is used to stop energy losses and control condensation drip from cold water plumbing and refrigeraton lines in one and two-family residential new construction and renovation work. Aerocel ® CG also efficiently reduces energy loss for hot water plumbing and liquid heating piping systems. The recommended temperature usage range for Aerocel ® CG Tube Insulation is -40°F to +220°F.
Resistance to Moisture Vapor Flow
The closed-cell structure of Aerocel-CG lnsulation effectively retard the flow of moisture vapor, and Aerocel-CG is considered a low transmittance vapor retarder protection.
Application
Aerocel ® CG Pipe Insulation, in unslit tubular form, can be slipped onto piping before it is connnected. Aerocel ® CG can also be slit lengthwise and snapped over piping that is already connected. Butt joints and all longitudinal seams are to be sealed with Aeroseal contact adhesive.
|
 |
|
 |