shahbaz Aerocel EPDM Thickness Recommendation Data
Aerocel EPDM Thickness Recommendation Data
Pipe Size Line Temp.
60°F (15.5°C)
Line Temp.
50°F (10°C)
Line Temp.
35°F (1.7°C)
Line Temp
0°F (-18°C)
3/8" ID Thru 3" IPS
Over 3" IPS
Based on Normal Condition Max 85°F (29.4°C) 70% RH*
1/4"* Wall
3/8"* Sheet
3/8" Wall
1/2" Sheet
1/2" Wall
3/4" Sheet
1" Wall
1-1/4" Sheet
3/8" ID Thru 3" IPS
Over 3" IPS
Based on Mild Condition Max 80°F (26.6°C) 50% RH**
1/4"* Wall
3/8"* Sheet
3/8" Wall
1/2" Sheet
3/8" Wall
3/4" Sheet
3/4" Wall
3/4" Sheet
3/8" ID Thru 3" IPS
Over 3" IPS
Over 10" IPS
Based on Severe Condition Max 90°F (32.2°C) 80% RH***
1/2" Wall
3/4" Sheet
3/4" Sheet
3/4" Wall
1" Sheet
1" Sheet
1" Wall
1-1/8" Sheet
1-1/8" Sheet
1-1/2" Wall
1-3/4" Sheet
2" Sheet
3/8" ID Thru 3" IPS
Over 3" IPS
Over 10" IPS
Based on Extremely Severe Condition Max 90°F (32.2°C) 85% RH****
3/4" Wall
1" Sheet
1" Sheet
1" Wall
1-1/4" Sheet
1-1/4" Sheet
1-1/4" Wall
1-1/2" Sheet
1-1/2" Sheet
2" Wall
2-1/2" Sheet
2-1/2" Sheet
* Although in some areas of the country, 1/4" and 3/8" wall thicknesses are recommended,
Aeroflex USA recommends 1/2" minimum wall thickness for optimum performance